33 (34) /45 Dual Fuel Generator

Speed: Low Speed
Cooling Cylinder: Water-Cooled
Fuel: Diesel Oil / Hfo / Natural Gas
Number of Strokes: Four-Stroke
Number of Cylinders: 8-Cylinder
Rated Electrical Power: 3000kw
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Zhejiang, China
to see all verified strength labels (7)

Basic Info.

Model NO.
DG3000 Dual Fuel Generator
Engine Capacity
3310kw
Fuel Consumption
187.5 L/H
Gas Consumption
646.9 Nm3/H
Transport Package
Wooden Case
Specification
9400*2600*4289 mm
Trademark
Ningbo diesel
Origin
Ningbo
Production Capacity
3000 Piecews/Year

Product Description

Main Specificatio
Generator Model DG3000 DG3200 DG3500
Rated Electrical Powe (kW) 3000 3200 3500
Engine Model DG8330ZD DG8340ZD2 DG8340ZD4
BorexStroke (mm) 330X450 340X450 340X450
Engine Type 4-Stroke, Inline, Direct Injection,Turbocharged, Intercooled
Engine Capacity (kW) 3310 3500 3850
                   Engine Rev. (rpm) 600 600 600
Fuel Consumption (L/h) 187.5 201.2 218
Gas Consumption (Nm3/h) 646.9 694.1 752
Note: All engine rating data based on ISO 3046/1;
Reference conditions: Ambient temperature 25ºC, Total Barometric Pressure 100kPa, Relative humidity 30%, Intercooler coolant inlet temperature 25 ºC;
Fuel characteristics: Related density: 0.84±0.005, Lower heat value:42700kj/kg, Consumption tolerance: +5%;
Power: An overload of 10% is permitted for one hour in every twelve hours of operation.

Characteristics:
Meet with: ISO8528, IEC60034, ISO3046; 
Brushless self excited alternator with AVR; 
Precise gas injection dual fuel system; 
Diesel oil / HFO / Natural gas use;
Low cost of operating and maintenance.

Electrical Performance:
Voltage Voltage no load adjustment range % 95~105
Voltage fluctuation rate % ±1
Stable voltage regulating rate % ±2.5
Transient voltage regulating rate % ±20~-15
Stabilizing time s 1
Alternator Excitation method   Brushless AVR
Frequency Stable frequency (rev.) regulating rate % 5
Frequency (rev.) fluctuation rate % ±0.5
Transient frequency regulating rate % ±10
Stabilizing time s < 5
Frequency regulating method   Auto / Manual
Protection Over speed   115% Nr   A, T, S   Reverse P.   -9.6% Pn   A, T
LO. P 0.25MPa A, 0.15MPa T,S   Over current  130% In     A, T
FW T. 90ºC A, 95ºC T,S   Over voltage 120% Vn     A, T
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now